BKTP 25-2500/10(6)-0.4 UHL1 Transformer Substation
The complete transformer substation in a block-modular building (BKTP) is designed to receive three-phase 50 Hz power at 6 or 10 kV, convert it to 0.4 kV, and supply it to consumers. It is used to power industrial plants. BKTP units are built to UHL1 climate rating per GOST 15150-69.
A BKTP consists of one or more block-modules mounted on foundations, with electrical connections fully assembled within the block(s). The block-modular building acts as a protective enclosure for the equipment installed inside. The building is fitted with lighting, heating and forced ventilation, controlled from an auxiliary-needs cabinet.
The walls of the module are made of 75 mm three-layer sandwich panels with coated galvanized steel cladding and non-combustible mineral-wool insulation. The base is a welded frame of rolled steel sections with guide rails for rolling the transformer in; where oil transformers are used, oil-collection pans sized for 20% of the oil volume are built in.
Technical specifications
| Power transformer rating | up to 2500 kVA |
| Rated HV voltage | 6 or 10 kV |
| Rated LV voltage | 0.4 kV |
| Climate rating | UHL1 per GOST 15150-69 |
| Wall sandwich-panel thickness | 75 mm |
Operating conditions
- Ambient temperature from −60°C to +40°C
- Average annual relative humidity 75% at +15°C
- Altitude not exceeding 1000 m above sea level
- Wind regions per SNiP 2.01.07-85
- Seismic resistance up to 8 points on the MSK-64 scale at elevations up to 25 m (9 points at ground level) per GOST 17516.1-90
BKTP must not be operated
- In explosive atmospheres or environments with caustic vapors/gases that degrade metal and insulation (unless forced supply ventilation is fitted)
- On mobile mine installations or other special-purpose equipment
Typical BKTP composition
- KTP substation per the customer's inquiry sheet
- Block-modular building per the agreed layout
- Stairs and platform for removing the transformer for repair (if specified)
- Additional equipment for installation in the modular building per the inquiry sheet
Key features
- Building lighting, heating and forced ventilation
- Auxiliary-needs cabinet for controlling building systems
- Guide rails and oil-collection pans for transformer service
- Seismic-resistant design
Send a request