Oil field

KTPND 25-250-10(6) U1 Transformer Substation for Oil Production

Complete transformer substations for oil production, outdoor type, are designed to receive 50 Hz industrial-frequency power at 10(6) kV, convert it to 0.4 kV, and supply it to oil production wells and other industrial facilities in temperate-to-harsh climate regions (from −45°C to +40°C).

The KTPND is supplied complete with a high-voltage disconnector, installed on the nearest power-line pole. The HV input to the substation is overhead; the outgoing 0.4 kV lines are cable-connected. Interlocks are provided to ensure safe operation by service personnel.

Send a request Back to catalog

Technical specifications

Rated HV voltage6(10) kV
Rated LV voltage0.4 kV
Number of outgoing lines6
Number of feeders1
Short-circuit withstand (dyn. / therm.)1.3–15.6 kA / 0.9–8.1 kA
Ingress protectionIP23
Weight without transformer315 kg
Climate rating−45°C to +40°C
Key technical specifications, KTPND 25-250/10(6) U1
Parameter254063100160250
Transformer power, kVA254063100160250
Rated HV current at 6 kV, A2.43.96.19.615.424
Rated HV current at 10 kV, A1.452.313.645.789.2514.45
HV fuse-link current at 6 kV, A810162031.540
HV fuse-link current at 10 kV, A5810162031.5
Rated LV current, A365891145231361

Key features

  • Overhead HV input, cable-connected 0.4 kV outgoing lines
  • Supplied complete with a pole-mounted HV disconnector
  • Personnel safety interlocks
  • Built for operation at oilfield sites in harsh climates

Send a request

KTPND 25-250-10(6) U1 Transformer Substation for Oil Production